Range: 90 RCD Range Modular circuit breakers for residual current protection
The 90 RCD range meets any ground fault protection requirement for any area of application.
The range comprises MDC compact residual current c.b. with overcurrent protection. (from 6 to 32 A, curves B and C, up to 10 kA and lΔn from 30 and 300 mA type AC, A, A[IR] and A[S] and F) BD and BDHP, add-on residual current devices for circuit breakers MT and MTHP (lΔn from 10 mA to 3 A type AC, A, A[IR], A[S] and A adjustable) IDP residual current circuit breakers (up to 125 A, lΔn from 10 to 500 mA type AC, A, A[IR], A[S], F, B).
IP41
Technical Info
Information
Download
Software
Certificates
DescriptionLocal residual current protection device (no socket)
CodeRCD
No. of poles1P+N
ColourBlack RAL 9005
Rated current16 A
Rated residual operating current30 mA
TypeA
Rated voltage (EN/IEC 61008-1, 61008-2-1)230/240 V
IP degreeIP41
Rated frequency (Hz)50Hz
RCD DelayWithout time delay
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII
Nominal making and breaking capacity500 A
Rated conditional short-circuit current3.000 A
Section rigid cableMin 1,5 mm² - Max 2,5 mm²
Section flexible cableMin 1,5 mm² - Max 2,5 mm²
Terminal typeWithout screws
Assembly positionFlush type or surface type
Operating temperature-5° - +40° (acc. To IEC),
-25° - +40° (acc. To EN)