Range: MSX Moulded case circuit breakers for power distribution
The moulded case circuit breakers MSX range is made up of circuit breakers with thermo-magnetic release, circuit breakers with thermo-magnetic release and Overcurrent Protection, circuit breakers with electronic release and switch disconnectors.
Technical Info
Information
Download
Software
Certificates
DescriptionInterruttore non automatico scatolato
CodeMSXM 1000
No. of poles3P
Rated current800 A
Release-
ELECTRICAL CHARACTERISTICS-
MECHANICAL CHARACTERISTICS-
StandardIEC/EN 60947-2
ExecutionFixed - Plug-in
Use categoryAC-23A, DC-22A
DIN rail mountingNo
Rated frequency (Hz)50 / 60
Can be equipped with motor operatorSì
Rated operating voltage (Ue)690 Vac - 250 Vdc
Compatible interlockLever – Cable
Rated impulse withstand voltage (Uimp)8 kV
Terminals suppliedFront FC
Overvoltage categoryIV
Assembly positionAny
Insulation voltage (Ui)800 V
Upline/downline power supplySì
Thermal regulation-
Electrical life (415Vac)4.000 cycles
Magnetic regulation-
Mechanical life10.000 cycles
Neutral protection-
Operating temperature-5°C +65°C
Total power loss153.6 W
Stocking temperature-20° +65°
Rated short-circuit current making capacity (Icm)17
Weight (kg)8.5
Rated short-time withstand current for 0,3s (Icw)10 kA