Range: 40 CD Range Surface-mounting distribution boards and enclosures
The 40CD Series of control units, available in transparent or blind door versions and in sizes from 8 to 72 modules, guarantees aesthetic integration with all types of furniture. The offer includes: 40CDK - IP65 watertight panels with removable frame (from 24M) and lead-in panels; accessories with wiring ducts, locks, aesthetic covers and blind panels, 40CD - IP55 watertight control units with drilling doilies on the walls, door with lock for each modular row; 40CD control units protected by furniture - IP40 up to 72M in the smoke and blind door versions; 40CD control units without door - IP40. All materials are Halogen Free.
IP65
IK09
650 °C
70 °C
Technical Info
Information
Download
Software
Certificates
Insulation classII (according to IEC 61140 standards)
ColourGrey RAL 7035
Outer dim. LxHxD (mm)410x878x160
IP degreeIP65
Dispersible power (W)89
Mechanical resistanceIK09
Rated voltage400 V
Door colourSmoked Transparent
No. of modules EN 5002272 (18x4)
Rated current125 A
Glow Wire Test650 °C
Operating temperature-25 +60 °C
Type of materialHalogen-free in compliance with EN 60754-2
Thermo-pressure with ball70 °C
Accessories for insulation restoringScrewcaps (GW44623) or fixing brackets in resin (GW44621)
StandardEN 60670-1 (CEI 23-48) IEC60670-24 CEI 23-49
Insulation voltage1000 V according to EN 62208 both in ac as well as in dc
ACCESSORIES SUPPLIED: screwcaps and module masks, circuit labels. Self-adhesive label to be filled out for certification according to standard CEI 23-51. NOTES: Dispersible power calculated according to CEI 23-49. For the perforations, use the GW52401 milling cutter. To restore the double insulation, use the relative accessories supplied (module masks and screwcaps) or the brackets for surface-mounting (GW44621). For applications in the photovoltaic environment, use the surface-mounting brackets - code GW44621. CHARACTERISTICS: removable and plumbable panels with windows. Thermo-pressure with ball equal to 70°C. INSTALLATION: for the possible enclosure-terminal block combinations, refer to the summary "COMPATIBILITY OF SURFACE-MOUNTING ENCLOSURES WITH BIPOLAR AND UNIPOLAR TERMINAL BLOCKS" in the selection guides of 40CD range.