Description
Automatic reclosing device
Code
ReStart Rm TOP
Suitable for
Int.magnetotermici diff. MDC/MT+BD e magnetotermici MTC/MT
Rated voltage
230 V
Rated current
max 63 A (MT) max 32 A (MDC-MTC)
Rated frequency (Hz)
50 Hz
Distribution system
TT - TN
No. of modules EN 50022
4
Insulation voltage (Ui)
500 V
Rated impulse withstand voltage (Uimp)
4 kV
Overvoltage category
III
Dielectric strength test voltage between pole and earth
2500 V ac for 1 minute
Type of residual current protection
AC - A - A[IR] - A[S]
Rated residual operating current
30 - 300 - 500 - 1000 mA
Operating temperature
-25 +60 °C
Stocking temperature
-40°C ÷ +70°C
Rated non-operating resistance between live parts and earth (Rdo)
8 kΩ (30 mA) - 2,5 kΩ (300-500-1000 mA)
Rated operating resistance between live parts and earth (Rd)
16 kΩ (30 mA) - 5 kΩ (300-500-1000 mA)
Rated non-operating resistance between live parts (Rcco)
0,3 Ω
Rated operating resistance between live parts (Rcc)
1,8 Ω
Type of contacts
1 x Photomos and 1 x Changeover
Voltage operating
Photomos: 5-230 V ac/dc Changeover: 230 V ac -30 V dc
Current operating
Photomos: 0.6 mA (min)-100 mA cosϕ=1 (max) Changeover: 1.5 mA ac - 0.8 mA dc
Use category
AC12
Operating modes
Photomos: NO/NC/Intermittent Changeover: CO
Terminal section
≤ 2,5 mm²
Rated tightening torque
0,4 Nm
Automatic reclosure for untimely tripping
Yes (can be excluded)
Earth failure test
Yes (can be excluded)
Short circuit test
Yes (can be excluded)
Settable insulation threshold
Yes
Continuous system monitoring
Yes (can be excluded)
Settable reclosing mode
Yes (optional) - automatic, with system control (ReStart function) - automatic for attempts (adjustable, from 0 to 10 attempts)
- remotely (impulse duration ≥ 200ms)
- automatic reclosing standby time, adjustable from 0 sec. to 1 hour
Ware Number