Range: 40 CD Range Surface-mounting distribution boards and enclosures
The 40CD Series of control units, available in transparent or blind door versions and in sizes from 8 to 72 modules, guarantees aesthetic integration with all types of furniture. The offer includes: 40CDK - IP65 watertight panels with removable frame (from 24M) and lead-in panels; accessories with wiring ducts, locks, aesthetic covers and blind panels, 40CD - IP55 watertight control units with drilling doilies on the walls, door with lock for each modular row; 40CD control units protected by furniture - IP40 up to 72M in the smoke and blind door versions; 40CD control units without door - IP40. All materials are Halogen Free.
IP65
IK09
650 °C
70 °C
Technical Info
Information
Download
Software
Certificates
Insulation classII (according to IEC 61140 standards)
ColourGrey RAL 7035
Outer dim. LxHxD (mm)298x420x140
IP degreeIP65
Dispersible power (W)32
Mechanical resistanceIK09
Rated voltage400V
Door colourSmoked Transparent
No. of modules EN 5002224
No. of modules EN 5002224 (12X2)
Rated current125 A
Glow Wire Test650 °C
Operating temperature-25 +60 °C
Type of materialHalogen-free in compliance with EN 60754-2
Thermo-pressure with ball70 °C
Accessories for insulation restoringScrewcaps (GW44623) or fixing brackets in resin (GW44621)
StandardEN 60670-1 (CEI 23-48) IEC60670-24 CEI 23-49
Insulation voltage1000 V according to EN 62208 both in ac as well as in dc
ACCESSORIES SUPPLIED: screwcaps and module masks, circuit labels. Self-adhesive label to be filled out for certification according to standard CEI 23-51. NOTES: Dispersible power calculated according to CEI 23-49. For the perforations, use the GW52401 milling cutter. To restore the double insulation, use the relative accessories supplied (module masks and screwcaps) or the brackets for surface-mounting (GW44621). For applications in the photovoltaic environment, use the surface-mounting brackets - code GW44621. CHARACTERISTICS: removable and plumbable panels with windows. Thermo-pressure with ball equal to 70°C. INSTALLATION: for the possible enclosure-terminal block combinations, refer to the summary "COMPATIBILITY OF SURFACE-MOUNTING ENCLOSURES WITH BIPOLAR AND UNIPOLAR TERMINAL BLOCKS" in the selection guides of 40CD range.