MSX Range
Moulded case circuit breakers for power distribution
The moulded case circuit breakers MSX range is made up of circuit breakers with thermo-magnetic release, circuit breakers with thermo-magnetic release and Overcurrent Protection, circuit breakers with electronic release and switch disconnectors.
UW ZOEKOPDRACHT
MSXc - Compact moulded case circuit breakers
MSX 160c - Compact moulded case circuit breakers up to 160 A - 16 kA
NOTES: or mounting on EN 50022 DIN rail, choose the fixing bracket GWD8875.
The space taken up on the EN 50022 DIN rail is approximately 4 modules for 3P versions and 6 modules for 3P+N versions. ACCESSORIES SUPPLIED: 225A ÷ 100A versions supplied with front terminals for copper cables (FW).
125A and 160A versions supplied with front terminals (FC). CHARACTERISTICS: adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii:
25A-40A: Ii = 600A
63A-80A: Ii = 1000A
100-125A: Ii = 1500A
160A: Ii = 1600A
MSX 160c - Compact moulded case circuit breakers up to 160 A - 25 kA
NOTES: or mounting on EN 50022 DIN rail, choose the fixing bracket GWD8875.
The space taken up on the EN 50022 DIN rail is approximately 4 modules for 3P versions and 6 modules for 3P+N versions. ACCESSORIES SUPPLIED: 225A ÷ 100A versions supplied with front terminals for copper cables (FW).
125A and 160A versions supplied with front terminals (FC). CHARACTERISTICS: adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii:
25A-40A: Ii = 600A
63A-80A: Ii = 1000A
100-125A: Ii = 1500A
160A: Ii = 1600A
MSX 250c - Compact moulded case circuit breakers up to 250 A - 16 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 3P+N versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release Ii:
160A: Ii = 5 ÷ 13 x In
250A: Ii = 5 ÷ 11 x In
MSX 250c - Compact moulded case circuit breakers up to 250 A - 25 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 3P+N versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release Ii:
160A: Ii = 5 ÷ 13 x In
250A: Ii = 5 ÷ 11 x In
MSX - Moulded case circuit breakers
MSX 125 - Moulded case circuit breakers up to 125 A - 36 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 5 modules for 3P versions and 7 modules for 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release Ii:
20A ÷100A: Ii = 6 ÷ 12 x In
125A: Ii = 6 ÷ 10 x In
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 5 modules for 3P versions and 7 modules for 4P versions. ACCESSORIES: supplied with front terminals (FC). CHARACTERISTICS: Adjustable magnetic release li:
20A ÷ 100A: Ii = 6 ÷ 12 x In
125A: Ii = 6 ÷ 10 x In.
MSX 125 - Moulded case circuit breakers up to 125 A - 65 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 5 modules for 3P versions and 7 modules for 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release Ii:
20A ÷100A: Ii = 6 ÷ 12 x In
125A: Ii = 6 ÷ 10 x In
MSX 160 - Moulded case circuit breakers 160 A - 36 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release: Ii = 6 ÷ 13 x ln
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 4P versions. ACCESSORIES: supplied with front terminals (FC). CHARACTERISTICS: Adjustable magnetic release: Ii = 6 ÷ 13 x ln.
MSX 160 - Moulded case circuit breakers 160 A - 65 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release: Ii = 6 ÷ 13 x ln
MSX 250 - Moulded case circuit breakers 250 A - 36 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release: Ii = 6 ÷ 10 x ln
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 4P versions. ACCESSORIES: supplied with front terminals (FC). CHARACTERISTICS: Adjustable magnetic release: Ii = 6 ÷ 10 x ln.
MSX 250 - Moulded case circuit breakers 250 A - 65 kA
Adjustable thermal and adjustable magnetic release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for 3P versions and 8 modules for 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release: Ii = 6 ÷ 10 x ln
MSX 400 - Moulded case circuit breakers 400 A - 36 kA
Adjustable thermal and adjustable magnetic release
ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: adjustable thermal release Ir = 0.63 ÷ 1 x In Adjustable magnetic release Ii = 6 ÷ 12 x In
MSX 400 - Moulded case circuit breakers 400 A - 50 kA
Adjustable thermal and adjustable magnetic release
ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: adjustable thermal release Ir = 0.63 ÷ 1 x In
Adjustable magnetic release Ii = 6 ÷ 12 x In
MSXD 125 - Moulded case circuit breakers with residual current protection
MSXD 125 - MCCB's with residual current protection up to 125 A - 25 kA
Adjustable thermal, fixed magnetic and adjustable residual current protection release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 7 modules. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii:
20A ÷ 100A: Ii = 12 x In
125A: Ii = 10 x In
Residual current circuit breaker tripping (Idn) and delay (dt) thresholds are adjustable:
Idn (A): 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3
dt (ms): 0 - 60 - 200 - 400 - 700
MSXD 125 - MCCB's with residual current protection up to 125 A - 36 kA
Adjustable thermal, fixed magnetic and adjustable residual current protection release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 7 modules. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii:
20A ÷ 100A: Ii = 12 x In
125A: Ii = 10 x In
Residual current circuit breaker tripping (Idn) and delay (dt) thresholds are adjustable:
Idn (A): 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3
dt (ms): 0 - 60 - 200 - 400 - 700
MSXD 160 - MCCB's with residual current protection 160 A - 25 kA
Adjustable thermal, fixed magnetic and adjustable residual current protection release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 8 modules. ACCESSORIES: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii = 13 x ln
Residual current circuit breaker tripping (Idn) and delay (dt) thresholds are adjustable:
Idn (A): 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3
dt (ms): 0 - 60 - 200 - 400 - 700
MSXD 160 - MCCB's with residual current protection 160 A - 36 kA
Adjustable thermal, fixed magnetic and adjustable residual current protection release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 8 modules. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii = 13 x ln
Residual current circuit breaker tripping (Idn) and delay (dt) thresholds are adjustable:
Idn (A): 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3
dt (ms): 0 - 60 - 200 - 400 - 700
MSXD 250 - MCCB's with residual current protection 250 A - 25 kA
Adjustable thermal, fixed magnetic and adjustable residual current protection release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 8 modules. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii = 10 x ln
Residual current circuit breaker tripping (Idn) and delay (dt) thresholds are adjustable:
Idn (A): 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3
dt (ms): 0 - 60 - 200 - 400 - 700
MSXD 250 - MCCB's with residual current protection 250 A - 36 kA
Adjustable thermal, fixed magnetic and adjustable residual current protection release
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 8 modules. ACCESSORIES SUPPLIED : supplied with front terminals (FC). CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii = 10 x In
Residual current circuit breaker tripping (Idn) and delay (dt) thresholds are adjustable:
Idn (A): 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3
dt (ms): 0 - 60 - 200 - 400 - 700
MSXE - Electronic moulded case circuit breakers
MSXE 160 - MCCB's with electronic release up to 160 A - 36 kA
NOTES: it is not possible mounting on EN 50022 DIN rail. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% protected for 4P circuit breakers.
MSXE 160 - MCCB's with electronic release up to 160 A - 65 kA
NOTES: it is not possible mounting on EN 50022 DIN rail. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% protected for 4P circuit breakers.
MSXE 250 - MCCB's with electronic release 250 A - 36 kA
NOTES: it is not possible mounting on EN 50022 DIN rail. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% protected for 4P circuit breakers.
MSXE 250 - MCCB's with electronic release 250 A - 65 kA
NOTES: it is not possible mounting on EN 50022 DIN rail. ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% protected for 4P circuit breakers.
MSXE 400 - MCCB's with electronic release 400 A - 36 kA
ACCESSORIES: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% or 50% protected for 4P circuit breakers.
MSXE 400 - MCCB's with electronic release 400 A - 50 kA
ACCESSORIES: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% or 50% protected for 4P circuit breakers.
MSXE 630 - MCCB's with electronic release 630 A - 36 kA
ACCESSORIES SUPPLIED: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% or 50% protected for 4P circuit breakers.
MSXE 630 - MCCB's with electronic release 630 A - 50 kA
ACCESSORIES: supplied with front terminals (FC). CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% or 50% protected for 4P circuit breakers.
MSXE 1000 - MCCB's with electronic release up to 1000 A - 50 kA
ACCESSORIES SUPPLIED: supplied with front terminals (FC) for 800A versions. Supplied with extended front terminals (FB) for 1000A versions. Operating lever extension for manual closing and opening operations. CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% or 50% protected.
MSXE 1250 - MCCB's with electronic release 1250 A - 50 kA
NOTES: tthe codes with the final letter B indicate circuit breaker with cable mechanical interlock already fitted on it (cable for mechanical interlock to be ordered separately). ACCESSORIES SUPPLIED: operating lever extension for manual closing and opening operations. CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% or 50% protected.
MSXE 1600 - MCCB's with electronic release 1600 A - 50 kA
NOTES: tthe codes with the final letter B indicate circuit breaker with cable mechanical interlock already fitted on it (cable for mechanical interlock to be ordered separately). ACCESSORIES SUPPLIED: operating lever extension for manual closing and opening operations. CHARACTERISTICS: current regulation field Ir = 0.4 ÷ 1 x In.
Neutral 100% or 50% protected.
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8875.
The space taken up on the EN 50022 DIN rail is approximately 4 modules for the 3P versions and 6 modules for the 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC).
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 6 modules for the 3P versions and 8 modules for the 4P versions. ACCESSORIES SUPPLIED: supplied with front terminals (FC).
NOTES: the codes with the final letter B indicate MMCB's with mechanical interlock wire already mounted (interlock cable to be ordered separately). EQUIPMENT: operating lever extension for manual closing and opening operations.
NOTES: the codes with the final letter B indicate MMCB's with mechanical interlock wire already mounted (interlock cable to be ordered separately). ACCESSORIES SUPPLIED: operating lever extension for manual closing and opening operations.
APPLICATIONS: used in order to signal the position ON or OFF of the MCCB's. CHARACTERISTICS: they are identified by the grey colour and with the AX symbol on the product.
APPLICATIONS: used in order to indicate the circuit breaker tripping status. NOTES: GWD8502 must be placed to the left of the circuit breaker lever.
GWD8503 must be placed to the right of the circuit breaker lever. CHARACTERISTICS: they are identified by the grey and black colours and with the AL symbol on the product.
APPLICATIONS: allows the remote release of a MCCB'S when a certain voltage is applied to its terminals. When the release is powered, the contacts and the operating lever of the MCCB's assume the tripped position. NOTE: The operating voltage range is 85% to 110% in AC and 75% to 125% in DC. CHARACTERISTICS: they are identified by the grey colour and the SH symbol on the product.
APPLICATIONS: allows the remote tripping of a RCBO's of MSXD series via NO push button connected. NOTE: voltage-independent release unit.
The release unit must be positioned external on the right side of the MCCB's.
APPLICATIONS: allows the remote release of a MCCB'S when the voltage applied to its terminals is between 35% and 70% of its rated voltage. When the release is not powered, the contacts and the circuit breaker operating lever assume the tripped position. NOTE: they prevent the circuit breaker from closing until the voltage is greater than at least 85% of its rated voltage. CHARACTERISTICS: They are identified by grey and black colours and with the UV symbol on the product.
APPLICATIONS: n order to allow remotely tripping of a circuit breaker when the voltage applied to its terminals is between 35% and 70% of its rated voltage. When the undervoltage release is not supplied, the contacts and the circuit breaker lever assume the circuit breaker tripping status. NOTE : they prevent the closing of circuit breaker until the voltage exceeds at least 85% of its rated voltage.
The undervoltage release must be mounted outside, to the right of the crcuit breaker. CHARACTERISTICS: They have 500ms delay time.
APPLICATIONS: allows the MCCB'S remote opening and closing depending on the electrical signals received. CHARACTERISTICS: to be mounted on the front of the MCCB's.
NOTE: to create the lever interlock system it is necessary to provide and install both the left and right interlocks, depending on the size of the switch. It is suggested to use rotary handles or motor operators for circuit breakers MSX/E/M 400-630 and MSXE/M 1000. CHARACTERISTICS: mechanism to be fixed on the front of both equal size 3 or 4 poles circuit breakers.
NOTE: the wire interlock consists of two mechanisms connected by a steel cable. The mechanisms are fixed on two circuit breakers, limited by the length and bending capacity of the wire. To create the wire interlock system it is necessary to provide and install a mechanism for each interlocked circuit breaker.
The cable is to be ordered separately. It is suggested to use rotary handles or motor operators for circuit breakers MSX/E/M 400-630 and MSXE/M 1000. CHARACTERISTICS: mechanism to be fixed on the front of both 3 or 4 pole circuit breakers (also with different sizes).
The circuit breakers can be placed in separate cubicles and at different heights.
APPLICATIONS: allows the circuit breaker lever to be locked in the ON or OFF status using up to 3 padlocks. NOTE: tthe locking devices for models 125A, 160A and 250A accept padlocks with a diameter of 5mm.
Locking devices for models from 400A to 1600A accept padlocks with a diameter of 8mm.
APPLICATIONS: allows the quick replacement of the switch, without the need to interfere with the connections. NOTE: to obtain the circuit-breaker in plug-in version, in addition to its fixes base, you need to provide the conversion kit. CHARACTERISTICS: the circuit breaker in the plug-in version is automatically locked in the base when the operating lever is in the ON position. It can't be removed until the operating lever is in the OFF or tripped position.
APPLICATIONS: allows the quick replacement of the of the MCCB's without the need to work on the connections. NOTE: tto obtain the circuit-breaker in plug-in version, in addition to the transformation kit, you need to provide its fixed base.
APPLICATIONS: to be considered in case of a MCCB's in plug-in version with internal accessories. Requires 1 plug for each internal accessory (auxiliary contact or opening release). NOTE: tto obtain the MCCB'S in plug-in version with internal accessories, in addition to the socket, a plug must be installed inside the fixed base.
Sockets for internal accessories mounted on plug-in MCCB's
APPLICATIONS: to be considered in case of a MCCB's in plug-in version with internal accessories. Requires 1 plug for each internal accessory (auxiliary contact or opening trip unit). Identical socket for each accessory type. NOTE: to obtain the MCCB'S in plug-in version with internal accessories, in addition to the socket, a plug must be installed inside the fixed base.
APPLICATIONS: ensure insulation between the phases of the circuit breaker terminals. NOTE: they cannot be mounted with terminal covers.
Dividers are supplied for each circuit breaker (2 pieces for 3P MCCBs and 3 pieces for 3P+N and 4P MCCBs). Additional divider can be ordered individually. All dividers can be mounted on either side (line and load) of a circuit breaker.
APPLICATIONS: allows automatic switchover between the power supply network (single-phase or three-phase) and the generator line. NOTE: for the correct functioning of the switchover control unit it is necessary
: -the power supply GWD8887
- 1 two positions built-in toggle handle switch with 2 contacts 1NO+1NC (preferably key)
- 2 fuse holders 3P+N (fuses 10.3x38) GW96312
- 2 fuse holders 2P (fuses 10.3x38) GW96302
- 1 contactor 2NO+2NC GWD6725
In addition, circuit breakers for protection of the power supply network and the generator line must each have the following accessories
: - 1 mechanical interlock (lever or cable)
- 1 motor operator
- 2 auxiliary contacts of position (AX)
- 1 auxiliary contact of fault indicator switch (AL) CHARACTERISTICS: equipped with a 4-line backlit display.
APPLICATIONS: supplies direct current power to the automatic switchover control unit GWD8886 when the power supply network fails by taking power from the generator or from the battery (optional). CHARACTERISTICS: the device can be mounted on DIN rail or plate.
Fout bij sturen van verzoek.
Probeer later opnieuw!
Dank u!
Uw aanvraag is met succes verstuurd
✕
Uw privacy is belangrijk voor ons
Gewiss gebruikt first party en third party cookies voor verschillende doeleinden: technische cookies om de website goed te laten werken (en waarvoor er geen toestemming van de gebruiker is vereist), functionele cookies om de door de gebruiker gekozen instellingen op te slaan, statistische cookies om te begrijpen hoe gebruikers op de website surfen en marketingcookies om gebruikers te volgen en interessante content aan hen aan te bieden. Door op 'X' te klikken kunt u verder surfen en alle andere cookies dan technische cookies weigeren; daarnaast kunt u uw keuzes op ieder ogenblik wijzigen via de knop 'Privacybeheer' in het Cookiebeleid. Raadpleeg tot slot onze Privacyverklaring voor meer informatie.
Gewiss en sommige derde partijen maken gebruik van cookies op cookies op 'gewiss.com'.
Gewiss gebruikt first party en third party cookies (respectievelijk cookies die rechtstreeks worden gegenereerd en beheerd door de eigenaar van de website waarop de gebruiker aan het surfen is, en cookies die worden gegenereerd en beheerd door andere partijen dan de eigenaar van de website) voor verschillende doeleinden. Door te klikken op 'Alles accepteren' geeft u toestemming voor alle cookies die behoren tot de hieronder aangegeven categorieën; als u daarentegen klikt op 'Ik bevestig mijn keuzes' geeft u toestemming voor het plaatsen van de categorieën cookies waarvoor u toestemming geeft.
Voorkeursbeheer:
+
Technische cookies
technical
Technische cookies zijn nodig om de website bruikbaar te maken, bijvoorbeeld door toegang te verlenen tot beschermde pagina's. Voor de werking ervan is geen toestemming van de gebruiker vereist. Zonder deze cookies kan het moeilijk of onmogelijk zijn om goed door de website te navigeren.
+
Functionele cookies
Met functionele cookies kan de website informatie opslaan die het gedrag of het uiterlijk ervan beïnvloedt op basis van verzoeken van de gebruiker. Voor de werking ervan is de toestemming van de gebruiker vereist.
+
Statistische cookies
Statistische cookies stellen ons in staat te begrijpen hoe gebruikers de website gebruiken en helpen ons bij het begrijpen van de belangrijkste vormen van interactie. Voor de werking ervan is de toestemming van de gebruiker vereist.
+
Marketing cookies
Marketingcookies worden gebruikt om bezoekers te volgen, bijvoorbeeld om inhoud te presenteren die voor een individuele gebruiker interessant is. Voor de werking ervan is de toestemming van de gebruiker vereist.
Verplicht veld
Controleer of de e-mail nog niet is gebruikt of of alle velden zijn verbeterd
Controleer uw e-mail
Het wachtwoord moet minimaal 6 en maximaal 12 tekens bevatten, een numeriek teken en een hoofdletter
Registratie is voltooid
Let op: gebruikersnaam en wachtwoord komen niet overeen
Voer een geldig e-mailadres in
De waarde komt niet overeen
Gegevenswijziging is succesvol afgerond
To fill the form you must be logged. Please go to
login page
E-mail succesvol verzonden
Ingeschreven
Dank u!
Uw aanvraag is met succes verstuurd
Authenticatiefout
Fout bij verzenden van aanvraag
Probeer later opnieuw!
User not found
Integration error
Neem contact op met de administrator
Je bent al geregistreerd op het evenement
Bekijk de kaart
Wachtwoord wijzigen is succesvol voltooid
Het wachtwoord moet minimaal 6 en maximaal 12 tekens bevatten, een numeriek teken en een hoofdletter
Voer de e-mail in het juiste veld in
Fout bij sturen van verzoek. Probeer later opnieuw!
Opslaan in de lijst
Voor de naam van, de catalogus in
Verlopen
Voor het downloaden van het bestand moet je tijdens de registratie een subtype kiezen, ga je naar het profiel wijzigen en kies je het!
Voor het downloaden van het bestand moet je een professionele installateur of groothandelaar zijn. Upgrade je profiel op mijn profielpagina!
For the download of the file you have to be a professionist installer or wholesaler, a designer or lighting designer. Upgrade your profile on my profile page!
GA
Verify code is expired, please try to login
The date must be of the indicated format
Lijst
Gemaakt door
Select
Account not yet confirmed, please confirm the link we sent you by mail